HUIRUIPU GT-H10-EX Gas Stationary Gas Alarm 0-100% LEL
Detection gas EX gas, range 0-100% LEL, resolution 1% LEL/1% VOL, alarm point low: 20; high: 50.
HuiRuiPu-
SUJIE SJ-100L Laser Dust Particle Counter 100L/min
$ 9841.00 -
HONEYEAGLE HNAG1000-NH3 Fixed Ammonia Gas Detector 0-15000PPM
$ 856.00 -
GUOYUGRA GY/VGD-200-NO-G (0-500ppm) nitric oxide Detector
$ 692.00 -
HONEYEAGLE HNAG1000-H2S Fixed hydrogen sulfide Detector 0-1000PPM
$ 347.00 -
KORNO MOT500-H2S-Y Online hydrogen sulfide alarm instrument 0-50ppm
$ 287.00
GT-H10 fixed gas alarm is used to detect the concentration of flammable gas or other toxic and harmful gases in the air, when the concentration reaches or exceeds the preset alarm value, the controller will send out an audible and visual alarm, timely remind to take safety measures, prevent explosion and poisoning accidents, so as to protect life and property safety.
This product adopts industrial-grade sensor, the instrument shell adopts a die-cast aluminum shell designed with explosion-proof and explosion-proof structure, and the groove design of the upper cover can lock the shell and the front of the sensorIt is designed as a downward structure to ensure that the sensor is in good contact with the gas, and the inlet adopts explosion-proof and waterproof joints. It can be widely used in metallurgy, petroleum, chemical industry, municipal and other industries。
peculiarity
Dustproof, explosion-proof, anti-static, anti-reverse connection, anti-interference, surge protection function;
Detection accuracy and range are adjustable;
Long life, high sensitivity, low drift, stable and reliable work;
Sensor fault self-check, two-level concentration alarm, with relay output function;
LCD display/digital display, working status indication;
Zero point automatic tracking, automatic temperature compensation, concentration over-range protection, multi-point calibration function;
At the same time, it supports two-wire (PowerBus), three-wire (4~20mA), four-wire (RS485) signal output and Lora/4G Internet of Things signal transmission
out, PLC, DCS and cloud platform can be uploaded;
Infrared remote control mode, the Detector can be adjusted without opening the cover, which is safe and convenient;
Pluggable module sensor design, convenient for later maintenance;
Flameproof design is suitable for hazardous conditions 1 and 2;
Serial models
| The gas to be measured | Measuring range | resolution | Alarm point |
| EX is combustible and combustible | 0-100%LEL | 1%LEL/1%VOL | Low: 20; High: 50 |
| O2 oxygen | 0-30%VOL | 0.1%VOL | Low: 19.5% VOL; High: 23.5% VOL |
| H2S hydrogen sulfide | 0-100PPM | 0.1PPM | Low: 10PPM; HEIGHT: 20PPM |
| CO carbon monoxide | 0-1000PPM | 1PPM | Low: 50PPM; HEIGHT: 150PPM |
| NO2 nitrogen dioxide | 0-20PPM | 0.1PPM | Low: 5PPM; HEIGHT: 10PPM |
| CO2, carbon dioxide | 0-5000PPM/0-5%VOL | 1PPM/0.1%VOL | Low: 2000; High: 4000 |
| NO nitric oxide | 0-250PPM | 1PPM | Low: 50PPM; HEIGHT: 150PPM |
| SO2 sulfur dioxide | 0-20PPM | 0.1/1PPM | Low: 5PPM; HEIGHT: 10PPM |
| CL2 chlorine | 0-20PPM | 0.1PPM | Low: 5PPM; HEIGHT: 10PPM |
| NH3 ammonia | 0-100PPM | 0.1/1PPM | Low: 20PPM; HIGH: 50PPM |
| H2 hydrogen | 0-1000PPM | 1PPM | Low: 50PPM; HEIGHT: 150PPM |
| PH3 phosphine | 0-20PPM | 0.1PPM | Low: 5PPM; HEIGHT: 10PPM |
| HCL hydrogen chloride | 0-20PPM | 0.1PPM | Low: 5PPM; HEIGHT: 10PPM |
| CLO2 chlorine dioxide | 0-50PPM | 0.1PPM | Low: 5PPM; HEIGHT: 10PPM |
HuiRuiPu GT-H10-EX Fixed gas alarmSpecifications
| LIST | VALUE |
|---|---|
| Range | 0-100%LEL |
| resolution | 1%LEL/1%VOL |
| alarm point | Low: 20; High: 50 |
HuiRuiPu GT-H10-EX Fixed gas alarm Packing list
[Note] Because the manufacturer's packaging may be updated or upgraded, the detailed packaging list shall be subject to the latest standard configuration of the manufacturer.


GT-H10-EX






